Please use this identifier to cite or link to this item: http://hdl.handle.net/1843/BUBD-AX3M7W
Type: Dissertação de Mestrado
Title: Monitoramento de afundamentos momentâneos de tensão e classificação por tipo, duração e magnitude
Authors: Patricia de Souza Carletto
First Advisor: Braz de Jesus Cardoso Filho
First Co-advisor: Igor Amariz Pires
First Referee: Thales Alexandre Carvalho Maia
Second Referee: Danilo Iglesias Brandao
Abstract: O Afundamento Momentâneo de Tensão, apesar de ser um fenômeno de curta duração, é um dos problemas mais comuns de degradação da Qualidade de Energia Elétrica no setor industrial, podendo causar interrupção do fluxo produtivo, refugos e atrasos. São caracterizados como uma redução nos valores de tensão (rms) para valores entre 0,1 a 0,9 pu (tensão residual), com duração entre 1 ciclo a 3 minutos. Como o afundamento ocorre em um ambiente industrial, muitos tipos de cargas são sensíveis aos afundamentos. O tipo de afundamento: monofásico, bifásico ou trifásico, tanto quanto a sua magnitude e tempo de duração, determinam as cargas suscetíveis aos afundamentos. Sendo assim, há necessidade de conhecer o perfil de ocorrência dos afundamentos para determinar a melhor solução de mitigação destes eventos. Esse trabalho apresenta o resultado de uma análise de 16 meses de monitoramento no Laboratório Tesla da UFMG, com o objetivo de fazer a caracterização desses afundamentos no período de setembro de 2015 a dezembro de 2016
Abstract: The momentary voltage sags, despite being a short-lived phenomenon, is one of the most usual problems of the degradation of Electrical Energy Quality in the industrial sector. It can cause interruption of the productive flow, generating losses of the items in the manufacturing process, as it rejects and delays it. Sags are characterized with a reduction in voltage values (rms) for values between 0.1 to 0.9 pu (residual voltage), lasting between 1 cycle and 3 minutes. Considering that the sags occur in an industrial environment, many types of loads are sensitive to them. The single-phase type, two-phase or three-phase sags, as well as their magnitude and duration determine the loads susceptibility. Besides that, it is also necessary to know the occurrence profile of the events to define the most appropriate mitigation solution for these sags. This works presents the results of 16 months monitoring analysis at the Tesla Laboratory of the UFMG, in order to know the characterizing of the sags, in the period from September/2015 to December/2016
Subject: Engenharia elétrica
Energia elétrica Qualidade
Afundamento de tensão
language: Português
Publisher: Universidade Federal de Minas Gerais
Publisher Initials: UFMG
Rights: Acesso Aberto
URI: http://hdl.handle.net/1843/BUBD-AX3M7W
Issue Date: 26-Sep-2017
Appears in Collections:Dissertações de Mestrado

Files in This Item:
File Description SizeFormat 
disserta__o_mestrado_1006_ppgee_patricia_de_souza_carletto_versao_cd.pdf27.68 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.