Title: Eliminação do R22, retrofit e novos fluidos refrigerantes com baixo GWP – estudo comparativo com os fluidos refrigerantes R-444B e R-454C
Other Titles: Elimination of R22, retrofit and new refrigerant fluids with low GWP – comparative study with refrigerant fluids R-444B and R-454C
Authors: Carlos Henrique Moreira Braga
Luiz Machado
Gabriela Cunha Bezerra
Juan José Garcia Pabon
Willian Moreira Duarte
Abstract: Os sistemas de climatização possuem grande importância na sociedade contemporânea, sendo necessário, portanto, avaliar seu impacto ambiental e a forma como eles se relacionam com a sustentabilidade do nosso planeta. O presente trabalho tem como objetivo avaliar o processo de substituição do fluido refrigerante R-22 em sistemas de climatização porfluidosrefrigerantes alternativos com baixos valores de GWP devido à grande quantidade de sistemas que ainda o utilizam, sobretudo em países em desenvolvimento, como o Brasil. De modo a permitir uma comparação efetiva entre os fluidos refrigerantes, foi elaborada uma metodologia para mensurar a capacidade de resfriamento, o coeficiente de performance e as taxas de transferência de calor em sistemas de climatização utilizando os fluidos R-22, R-444B e R-454C. Os resultados apresentam reduções médias entre 8,8% e 17,6% na capacidade de resfriamento e entre 6,8% e 8,8% no coeficiente de performance. Considerando o aspecto ecológico, com a utilização de fluidos que não agridem a camada de ozônio e com baixo impacto sobre o efeito estufa, o presente estudo demonstra a viabilidade do retrofit do R-22.
Abstract: Air conditioning systems are of great importance in contemporary society, and it is therefore necessary to evaluate their environmental impact and the way in which they relate to the sustainability of our planet. The present work aims to evaluate the process of replacing R-22 refrigerant in air conditioning systems by alternative refrigerants with low GWP values due to the large number of systems that still use it, especially in developing countries, such as Brazil. To allow an effective comparison between the refrigerants, a methodology was developed to measure, the cooling capacity, the coefficient of performance and heat transfer rates of air conditioning systems using the fluids R-22, R-444B and R-454C. The results show average reductions between 8.8% and 17.6% in the cooling capacity and between 6.8% and 8.8% in the coefficient of performance.Considering the ecological aspect, with the use of refrigerants that do not harm the ozone layer and with a low impact on the greenhouse effect, the present study demonstrates the viability of the retrofit of the R-22.
Subject: Fluidos refrigerantes
language: por
metadata.dc.publisher.country: Brasil
Publisher: Universidade Federal de Minas Gerais
Publisher Initials: UFMG
metadata.dc.publisher.department: ENG - DEPARTAMENTO DE ENGENHARIA MECÂNICA
Rights: Acesso Aberto
metadata.dc.identifier.doi: http://dx.doi.org/10.29327/xxiiconemi.569957
URI: http://hdl.handle.net/1843/57502
Issue Date: 5-Apr-2023
metadata.dc.url.externa: http://dx.doi.org/10.29327/xxiiconemi.569957
Appears in Collections:Artigo de Evento



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.