Título: Estudo comparativo de um ar condicionado convencional utilizando um fluido refrigerante alternativo ao R-410A para aplicação em escritórios
Título(s) alternativo(s): Comparative study of a conventional air conditioner using different refrigerant as an alternative for R-410A
Autor(es): Leonardo Victor Silva Martins
Tiago de Freitas Paulino
Ramon de Paoli Mendes
Luiz Machado
Willian Moreira Duarte
Resumen: Há um cronograma global para redução/banimento de diversos fluidos refrigerantes, em função de impactos ambientais. Entretanto, grande parte das unidades de refrigeração e climatização em países em desenvolvimento, como o Brasil, operam com o R-22. Com o intuito de reaproveitar esses equipamentos, é interessante avaliar fluidos alternativos que, com algumas modificações no sistema, possibilitem reaproveitalos. Em função disso, este trabalho comparou o COP durante um ano de um sistema de ar condicionado do tipo split utilizando o R-410A e o R-290, bem como o TEWI para ambos os fluidos. Para isso, foi utilizado um modelo matemático desenvolvido no Equation Engineering Solver (EES), englobando os componentes do sistema e a zona térmica. Adicionalmente, foram consideradas também as variações climáticas e os seus impactos nesse recinto avaliado. Por meio desse estudo, foi possível constatar que o R-290, quando comparado ao R-410A apresentou, em média, um COP 44% maior, com uma carga de refrigerante 45% menor, além de um TEWI 77% menor. Esses valores sugerem que, analisando do ponto de vista de desempenho e impacto ambiental (TEWI), o R-290 é uma alternativa bem interessante para o R-410A como substituto nesses equipamentos já existentes e mesmo para novos sistemas.
Abstract: There is a global schedule to reduce/ban various refrigerants, due to environmental impacts. There is a global schedule to reduce/ban various refrigerants, due to environmental impacts.However, most refrigeration and air conditioning units in developing countries, such as Brazil, operate with R22. In order to reuse this equipment, it is interesting to evaluate alternative fluids that, with some modifications in the system, make it possible to reuse them. As a result, this work compared the COP during one year of a split-type air conditioning system using R-410A and R-290, as well as TEWI for both fluids. For this, a mathematical model developed in the Equation Engineering Solver (EES) was used, encompassing the system components and the thermal zone. Additionally, climatic variations and their impacts on the evaluated enclosure were also considered. Through this study, it was possible to verify that R-290, when compared to R410A, presented, on average, a 44% higher COP, with a 45% lower refrigerant charge, in addition to a 77% lower TEWI. These values suggest that, from the point of view of performance and environmental impact (TEWI), R-290 is a very interesting alternative to R-410A as a replacement for these existing equipment and even for new systems. However, most refrigeration and air conditioning units in developing countries, such as Brazil, operate with R22. In order to reuse this equipment, it is interesting to evaluate alternative fluids that, with some modifications in the system, make it possible to reuse them. As a result, this work compared the COP during one year of a split-type air conditioning system using R-410A and R-290, as well as TEWI for both fluids. For this, a mathematical model developed in the Equation Engineering Solver (EES) was used, encompassing the system components and the thermal zone. Additionally, climatic variations and their impacts on the evaluated enclosure were also considered. Through this study, it was possible to verify that R-290, when compared to R410A, presented, on average, a 44% higher COP, with a 45% lower refrigerant charge, in addition to a 77% lower TEWI. These values suggest that, from the point of view of performance and environmental impact (TEWI), R-290 is a very interesting alternative to R-410A as a replacement for these existing equipment and even for new systems.
Asunto: Engenharia mecânica
Modelos matemáticos
Ar condicionado
Idioma: por
País: Brasil
Editor: Universidade Federal de Minas Gerais
Sigla da Institución: UFMG
Departamento: ENG - DEPARTAMENTO DE ENGENHARIA MECÂNICA
Tipo de acceso: Acesso Aberto
Identificador DOI: http://dx.doi.org/10.29327/xxiiconemi.563616
URI: http://hdl.handle.net/1843/57501
Fecha del documento: 5-abr-2023
metadata.dc.url.externa: http://dx.doi.org/10.29327/xxiiconemi.563616
Aparece en las colecciones:Artigo de Evento

archivos asociados a este elemento:
archivo Descripción TamañoFormato 
ESTUDO COMPARATIVO DE UM AR CONDICIONADO CONVENCIONAL UTILIZANDO UM FLUIDO - PDFA.pdf1.2 MBAdobe PDFVisualizar/Abrir


Los elementos en el repositorio están protegidos por copyright, con todos los derechos reservados, salvo cuando es indicado lo contrario.